With 2-wire/3-wire proximity sensors conforming to IEC 60947-5-2
Discrete output number
8
Discrete output type
Relay
Discrete output voltage
24 V 19...30 V DC 24...240 V 10...264 V AC
Discrete output current
2000 mA
Complementary
Sensor power supply
19...30 V
Voltage state 1 guaranteed
>,= 11 V
Current state 1 guaranteed
>,= 2 mA
Voltage state 0 guaranteed
<,= 5 V
Current state 0 guaranteed
<,= 1.5 mA
Input impedance
6800 Ohm
Insulation resistance
>, 10 MOhm 500 V DC
Power dissipation in W
<,= 3.1 W
DC typical filtering time
4 ms
DC maximum filtering time
7 ms
Response time on output
<,= 12 ms activation <,= 10 ms deactivation
Paralleling of inputs
No
Typical current consumption
100 mA at 3.3 V DC
MTBF reliability
912167 H
Protection type
1 external fuse per group of input channel 0.5 A fast blow Reverse polarity protection on input 1 external fuse per output channel or group of output channel fast blow
Voltage detection threshold
>, 18 V DC sensor OK <, 14 V DC sensor fault
Minimum switching current
1 mA 5 V DC
Maximum switching voltage
264 V AC 125 V DC
Mechanical durability
>,= 20000000 cycles
Electrical durability
300000 cycles DC-13 7.2 W 24 V 300000 cycles AC-15 60 VA 200 V 0.35 300000 cycles AC-15 36 VA 240 V 0.35 300000 cycles AC-14 80 VA 200 V 0.7 300000 cycles AC-14 72 VA 240 V 0.7 100000 cycles DC-13 24 W 24 V 100000 cycles AC-15 200 VA 200 V 0.35 100000 cycles AC-15 120 VA 240 V 0.35 100000 cycles AC-14 300 VA 200 V 0.7 100000 cycles AC-14 240 VA 240 V 0.7
Switching frequency
1 Hz
Status LED
1 LED red for module I/O 1 LED red for module error (ERR) 1 LED per channel green for channel diagnostic 1 LED green for module operating (RUN)
Product weight
0.135 kg
Environment
IP degree of protection
IP20
Standards
CSA C22.2 No 142 IEC 1131-2 IEC 664 NF C 63-850 UL 508 UL 746C
Dielectric strength
500 V DC 1 minute, between group of I/O 2830 V AC at 50/60 Hz 1 minute, output relay 1500 V AC at 50/60 Hz 1 minute, primary/secondary