Poles description | 3P |
Network type | AC |
Utilisation category | AC-3 |
Network frequency | 50/60 Hz conforming to IEC 60947-2 |
Mounting mode | By clips By screws |
Mounting support | Rail |
Mounting position | Any position |
Motor power kW | 4 kW at 690 V AC 50/60 Hz 3.7 kW at 500 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 2.2 kW at 400 V AC 50/60 Hz 1.1 kW at 230 V AC 50/60 Hz |
Breaking capacity | Icu : 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 Icu : 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 Icu : 2 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 Icu : >, 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 Icu : >, 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity | 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 |
Control type | Push-button |
Thermal protection adjustment range | 4...6.3 A |
Magnetic tripping current | 78 A |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
Power dissipation | 2.5 W per pole |
Mechanical durability | 100000 cycles |
Electrical durability | 100000 cycles AC-3 |
Operating rate | 25 cyc/h |
Connections - terminals | Screw clamp terminals:[Sapce] 2 cable(s) of 1...4 mm? (flexible)[Sapce] with cable end Screw clamp terminals:[Sapce] 2 cable(s) of 1.5...6 mm? (flexible)[Sapce] without cable end Screw clamp terminals:[Sapce] 2 cable(s) of 1...6 mm? (solid)[Sapce] |
Tightening torque | 1.7 N.m screw clamp terminals |
Height | 89 mm |
Width | 44.5 mm |
Depth | 88 mm |
Product weight | 0.26 kg |