Poles description |
3P
|
Network type |
AC
|
Utilisation category |
AC-3
|
Network frequency |
50/60 Hz conforming to IEC 60947-2
|
Mounting mode |
By clips
By screws
|
Mounting support |
Rail
|
Mounting position |
Any position
|
Motor power kW |
7.5 kW at 690 V AC 50/60 Hz
5.5 kW at 500 V AC 50/60 Hz
4 kW at 440 V AC 50/60 Hz
4 kW at 400 V AC 50/60 Hz
2.2 kW at 230 V AC 50/60 Hz
|
Breaking capacity |
Icu : 8 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Icu : 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Icu : 2 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
Icu : >, 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Icu : >, 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
|
[Ics] rated service short-circuit breaking capacity |
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
|
Control type |
Push-button
|
Thermal protection adjustment range |
6...10 A
|
Magnetic tripping current |
138 A
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
Power dissipation |
2.5 W per pole
|
Mechanical durability |
100000 cycles
|
Electrical durability |
100000 cycles AC-3
|
Operating rate |
25 cyc/h
|
Connections - terminals |
Screw clamp terminals:[Sapce] 2 cable(s) of 1...4 mm? (flexible)[Sapce] with cable end
Screw clamp terminals:[Sapce] 2 cable(s) of 1.5...6 mm? (flexible)[Sapce] without cable end
Screw clamp terminals:[Sapce] 2 cable(s) of 1...6 mm? (solid)[Sapce]
|
Tightening torque |
1.7 N.m screw clamp terminals
|
Height |
89 mm
|
Width |
44.5 mm
|
Depth |
88 mm
|
Product weight |
0.26 kg
|