Tripping current 130 % of Ir on two phase, the last one at 0 conforming to IEC 60947-4-1
Complementary
Product compatibility
LC1E06...38
Network type
AC
Network frequency
50...60 Hz
Mounting support
Rail (with specific accessories) Plate (with specific accessories) Under contactor
Overload tripping class
Class 10A conforming to IEC 60947-4-1
Signalling function
Relay trip indicator
Thermal protection adjustment range
2.5...4 A
Tripping threshold
1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Mechanical robustness
Vibrations: 3 Gn conforming to IEC 60068-2-6 Shocks: 6 Gn for 11 ms conforming to IEC 60068-2-7
Auxiliary contact composition
1 NO + 1 NC
[Ith] conventional free air thermal current
Control circuit : 5 A
[Ue] rated operational voltage
<,= 690 V AC
Associated fuse rating
Power circuit : 6 A (aM) Power circuit : 10 A (gG) Control circuit : 5 A (gG)
[Ui] rated insulation voltage
690 V conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV
Control type
Reset: green push-button Stop: red push-button
Temperature compensation
-20...60 °C
Connections - terminals
Screw clamp terminals (control circuit): 2 solid cable(s) without cable end of 1...2.5 mm? Screw clamp terminals (control circuit): 2 flexible cable(s) with cable end of 1...2.5 mm? Screw clamp terminals (control circuit): 2 flexible cable(s) without cable end of 1...2.5 mm? Screw clamp terminals (power circuit): 1 solid cable(s) without cable end of 1...6 mm? Screw clamp terminals (power circuit): 1 flexible cable(s) with cable end of 1...4 mm? Screw clamp terminals (power circuit): 1 flexible cable(s) without cable end of 1.5...6 mm?
Tightening torque
Control circuit (screw clamp terminals): 1.7 N.m Power circuit (screw clamp terminals): 1.7 N.m
Height
44.5 mm
Width
45 mm
Depth
70 mm
Product weight
0.13 kg
Environment
Standards
IEC 60947-4-1 IEC 60947-5-1
Product certifications
GOST
Protective treatment
TH conforming to IEC 60068
IP degree of protection
IP20 conforming to IEC 60529
Ambient air temperature for operation
-20...70 °C with derating -20...60 °C without derating conforming to IEC 60947-4-1