Voltage 1...5 V Voltage 0...5 V Voltage 0...10 V Voltage +/- 10 V Current 4...20 mA Current 0...20 mA
Analog/digital conversion
16 bits
Complementary
Nominal read cycle time
1 ms
Measurement error
0.4 % of full scale 4...20 mA 0...60 °C 0.4 % of full scale 1...5 V 0...60 °C 0.4 % of full scale 0...5 V 0...60 °C 0.4 % of full scale 0...20 mA 0...60 °C 0.2 % of full scale 4...20 mA 25 °C 0.2 % of full scale 1...5 V 25 °C 0.2 % of full scale 0...5 V 25 °C 0.2 % of full scale 0...20 mA 25 °C 0.2 % of full scale 0...10 V 0...60 °C 0.2 % of full scale +/- 10 V 0...60 °C 0.1 % of full scale 0...10 V 25 °C 0.1 % of full scale +/- 10 V 25 °C
Isolation between channels and bus
1000 Vrms
Isolation between channels and ground
1000 Vrms
Isolation between channels
Common point
Common mode between channels
None
Maximum overvoltage on input
-30...30 V at state 1 250 Ohm -15...15 V at state 0 250 Ohm
Electrical connection
1 connector SUB-D 25
Overcurrent
-30...30 mA at state 1 250 kOhm
Marking
CE
Current consumption
500 mA 5 V DC
Module format
Standard
Product weight
0.33 kg
Environment
Standards
IEC 1131
Product certifications
ABS BV DNV GL LR RINA RMRS
Ambient air temperature for operation
0...60 °C
Ambient air temperature for storage
-25...70 °C
Relative humidity
5...95 % without condensation for storage 10...95 % without condensation for operation